Motor Power Output Connectors
DANGER: Before you do maintenance to the equipment, disconnect the electrical power. Wait at least ten (10) minutes after removing the power supply before doing maintenance or an inspection. Otherwise, there is the danger of electric shock.
The drive can be used to drive the following motor types:
- Brushless (refer to Brushless Motor Connections)
- DC Brush (refer to DC Brush Motor Connections)
- Stepper (refer to Stepper Motor Connections)
For a complete list of electrical specifications, refer to Electrical Specifications
DANGER: Shock and Fire Hazard
Electrical wiring must be designed and installed in accordance with local electrical safety regulations to prevent the risk of fire and electrical shock.
Table: Motor Power Output Connector Pinout
Pin |
Description |
Connector |
---|---|---|
|
Motor Ground |
|
A |
Motor Phase A Output | |
B |
Motor Phase B Output | |
C | Motor Phase C Output |
Table: Motor Power Output Mating Connector Ratings
Specification | Description | |
---|---|---|
Type | 4-Pin Terminal Block | |
Part Numbers | Aerotech: ECK02593 | |
Phoenix: 1756298 | ||
Conductor Cross Section |
One conductor, stranded with ferrule and plastic sleeve | 14...22 AWG (0.25...2.5 mm2) |
Two conductors (same cross-section), stranded, twin ferrule with plastic sleeve | 16...20 AWG (0.5...1.5 mm2) | |
Tightening Torque | 0.5...0.6 N·m | |
Conductor Insulation Strip Length | 7 mm (0.25 in) | |
(1) Refer to the manufacturer website for additional information. (2) Motor wires should be sized based on the motor supply input fuse value. Upstream fusing and/or circuit breakers can be used for additional protection. |