SignalLogAxes Parameter

Default Value: 15

Minimum Value: None

Maximum Value: None

Units: None

Type: int

IMPORTANT: You must reset the controller for these changes to have an effect. If you set this parameter from an AeroScript program, the controller does not set the active value and this parameter does not have an effect on program execution.

Use the SignalLogAxes parameter to specify the mask of axes that Signal Log monitors. When Signal Log is enabled, it collects a circular buffer of data from the axes that you specify for this parameter.

Signal Log is triggered when the controller generates an axis fault from the SignalLogFaultMaskTrigger Parameter on an axis that you specify for the SignalLogAxes parameter.

Tip: This parameter requires memory allocation. If the memory allocation fails, a memory allocation error occurs. If memory resources are low, you can decrease the value of this parameter to release memory for other Automation1 features.