Electrical Specifications
Table: Electrical Specifications (Common)
Table: Electrical Specifications (by Ordering Option)
Input Voltage Option | -240V1 | -480V2 | -480V1 | ||||
---|---|---|---|---|---|---|---|
Output Current Option | -50 | -100 | -10 | -20 | -30 | -50 | -100 |
Motor Supply Input Current |
20 A | 30 A | 6 A | 10 A | 15 A | 24 A | 30 A |
Motor Supply Maximum overload protection breaker |
30 A | 30 A | |||||
Motor Supply Input Voltage Max (1,2) |
208-240 VAC |
480Y/277 VAC(3) |
|||||
Output Current (peak) (4) | 50 A | 100 A | 10 A | 20 A | 30 A | 50 A | 100 A |
Output Current (continuous)(4,5) | 17.7 ARMS | 35.4 ARMS | 3.5 ARMS | 7.1 ARMS | 10.6 ARMS | 17.7 ARMS |
21.1 ARMS(6) 35.4 ARMS(7) |
Peak Output Voltage | 340 V | 390 V | |||||
MOTOR: Electronic Overcurrent Shutoff | 100 A | 200 A | 100 A | 100 A | 100 A | 200 A | 200 A |
SHUNT: Electronic |
50 A | 100 A | 50 A | 50 A | 50 A | 100 A | 100 A |
Internal Motor Supply Capacitance | 4800 µF | 1500 µF | |||||
Capacitor Safe Discharge Time | 10 minutes (verify <50 VDC at DC bus terminals) | ||||||
(1) TN configuration only. (2) The iXC6e/XC6e requires three phase motor supply power. (3) The XC6-480V1 or -480V2 drive must be connected only to a grounded wye-source where the maximum voltage does not exceed 277 VAC to ground. (4) There are three motor output phases from the drive. (5) These values are under full output power. Under a lighter load, the continuous output current capability will be higher. (6) Specification for 20 kHz PWM switching frequency. (7) Specification for 10 kHz PWM switching frequency. |
Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit protection must be provided in accordance with the National Electrical Code and any additional local codes.
WARNING: Electric Shock or Fire Hazard! A fault current interruption could be the result of an open branch-circuit protective device. To reduce the risk of fire or electric shock, examine the current-carrying parts and other controller components. Replace all damaged parts. If a burnout of the current element of an overload relay occurs, you must replace the complete overload relay.
AVERTISSEMENT : Risque d'électrocution ou d'incendie ! Une interruption du courant de défaut peut être provoqué par un dispositif de protection de circuit de dérivation ouvert. Pour réduire le risque d'incendie ou d'électrocution, examinez les pièces conductrices de courant et les autres composants du contrôleur. Remplacer toutes les parties endommagées. Si un grillage de l'élément de courant d'un relais de surcharge se produit, vous devez remplacer le relais de surcharge dans son ensemble.