Electrical Specifications

Table: Electrical Specifications (Common)

Description Specification
Control Supply

Input Voltage

100-240 VAC (±10%)

Input Frequency

50-60 Hz

Inrush Current

68 APK @ 240 V

Input Current

0.5 ARMS

Internal Fuse 2 A/250 V, 35 A interrupt rating, L terminal only
External Breaker 20 A maximum (Type-C)
SCCR Suitable for use on a circuit capable of delivering not more than 5,000 rms symmetrical amperes, 240 volts maximum
Power Amplifier Bandwidth 2500 Hz maximum (software selectable)
PWM Switching Frequency 20 kHz
Minimum Load Inductance 0.5 mH
User Power Supply Output 5 VDC (@ 500 mA)
Motor Type Brushless, Brush, Stepper
Protective Features
  • Output short circuit
  • Peak over current
  • DC bus over voltage
  • Motor RMS over current
  • Motor over temperature
  • Heatsink over temperature
  • Control power supply under voltage
  • IGBT supply under voltage
  • Shunt resistor monitoring
Insulation Over Voltage Category 3
Conductors Copper Only, 75 °C (1)

(1) The wire temperature rating could be higher than 75 °C. The 75 °C reference is for end-use installers when sizing the conductors per NFPA 70 NEC (National Electrical Code) where applicable.

Table: Electrical Specifications (by Ordering Option)

Output Current Ordering Option -10 -20 -30
Motor Supply Input Current at full output power 5 A 10 A 10 A
Motor Supply Input Voltage Max(1,2)
(Vrms AC1 to AC2, +10%)
240 VAC
50/60 Hz
Output Current (peak) (3) 10 A 20 A 30 A
Output Current (continuous)(3,4) 3.5 ARMS 5.3 ARMS 5.3 ARMS
Internal time delay fuse (AC1 input only) 5 A 10 A 10 A
Peak Output Voltage 340 V
Maximum Motor Supply External Breaker 20 A maximum (Type-D)
Internal Motor Supply Capacitance 1200 µf
Capacitor Safe Discharge Time (to 50 V) 10 minutes
Shunt / Brake Internal Fuse 8 A

(1) The iXC4/XC4 uses a single phase motor supply power.

(2) A Lower motor supply voltage may be used. This will result in a reduction of output power.

(3) There are three motor output phases from the drive.

(4) These values are under full output power. Under a lighter load, the continuous output current capability will be higher.

Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit protection must be provided in accordance with the National Electrical Code and any additional local codes.

WARNING: Electric Shock or Fire Hazard! A fault current interruption could be the result of an open branch-circuit protective device. To reduce the risk of fire or electric shock, examine the current-carrying parts and other controller components. Replace all damaged parts. If a burnout of the current element of an overload relay occurs, you must replace the complete overload relay.

AVERTISSEMENT : Risque d'électrocution ou d'incendie ! Une interruption du courant de défaut peut être provoqué par un dispositif de protection de circuit de dérivation ouvert. Pour réduire le risque d'incendie ou d'électrocution, examinez les pièces conductrices de courant et les autres composants du contrôleur. Remplacer toutes les parties endommagées. Si un grillage de l'élément de courant d'un relais de surcharge se produit, vous devez remplacer le relais de surcharge dans son ensemble.